Schneider Electric

Schneider Electric GV4PE02N6 Motor circuit breaker, TeSys GV4, 3P, 2A, Icu 50kA, thermal magnetic, lugs terminals

(No reviews yet) Write a Review
SKU:
GV4PE02N6
MPN:
GV4PE02N6
Condition:
New
Device Application:
motor protection
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Magnetic Tripping Current:
34-34 A
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Environmental Disclosure:
ENVPEP1704004EN
Fire Resistance:
960°C IEC 60695-2-11
Trip Unit Technology:
thermal-magnetic || electronic
Weight:
1.45 kg
Mechanical Durability:
40000 cycles
Eu Rohs Directive:
Compliant with Exemptions
Poles Description:
3P
Ambient Air Temperature For Operation:
-25-70°C
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Device Short Name:
GV4PE
Product Or Component Type:
motor circuit breaker
Warranty:
18 months
Circularity Profile:
ENVEOLI1704004EN
Phase Failure Sensitivity:
yes IEC 60947-4-1
Connections - Terminals:
lugs-ring terminals
Ambient Air Temperature For Storage:
-50-85°C
Sustainable Offer Status:
Green Premium product
Operating Position:
any position
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Rohs Exemption Information:
Yes
Halogen Content Performance:
Halogen free plastic parts product
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Power Dissipation Per Pole:
4.6 W
Connection Pitch:
27 mm without spreaders || 35 mm with spreaders
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Motor Power Kw:
0.25-0.25 kW 400...415 V AC 50/60 Hz || 0.37-0.37 kW 400...415 V AC 50/60 Hz || 0.55-0.55 kW 400...415 V AC 50/60 Hz || 0.75-0.75 kW 400...415 V AC 50/60 Hz || 0.37-0.37 kW 500 V AC 50/60 Hz || 0.55-0.55 kW 500 V AC 50/60 Hz || 0.75-0.75 kW 500 V AC
Breaking Capacity:
100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 65 kA 208Y/120 V AC 50/60 Hz UL 60947 || 65 kA 240 V AC 50/60 Hz
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Maximum Operating Rate:
25 cyc/h
Line Rated Current:
0.0833333333333333
Standards:
CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
Range Of Product:
TeSys GV4
Product Name:
TeSys GV4 || TeSys Deca
Ik Degree Of Protection:
IK07 IEC 62262
Depth:
116 mm
Color:
Gray RAL 7016)
Suitability For Isolation:
yes IEC 60947-1
Country of Origin:
Poland
Climatic Withstand:
IACS E10
Range:
TeSys Deca
Control Type:
toggle
Rated Duty:
continuous IEC 60947-4-1
$1,117.50

Description

TeSys GV motor circuit breaker, 3 poles (3P), 2A/690V, for protection of 3-phase motors 0.25-0.75kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection for bars or cables with lugs. Thermal protection adjustable by dials with a setting current Ir in range 0.8-2A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).