Schneider Electric GV4PE115B Motor circuit breaker, TeSys GV4, 3P, 115A, Icu 25kA, thermal magnetic, Everlink terminals
Schneider Electric
$695.00
TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
- Environmental Disclosure:
- ENVPEP1704004EN
- Country of Origin:
- United States
- Weight:
- 1.45 kg
- Net Weight:
- 1.45 kg
- Rated Duty:
- continuous IEC 60947-4-1
- Control Type:
- toggle
- Standards:
- CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
- Circularity Profile:
- ENVEOLI1704004EN
- Magnetic Tripping Current:
- 1955-1955 A
- Connections - Terminals:
- EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Pollution Degree:
- 3
- Warranty:
- 18 months
- Ip Degree Of Protection:
- IP40 IEC 60529
- Suitability For Isolation:
- yes IEC 60947-1
- Fire Resistance:
- 960°C IEC 60695-2-11
- Maximum Operating Rate:
- 25 cyc/h
- Operating Position:
- any position
- Range Of Product:
- TeSys GV4
- Motor Power Kw:
- 37-37 kW 400...415 V AC 50/60 Hz || 45-45 kW 400...415 V AC 50/60 Hz || 55-55 kW 400...415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 55-55 kW 500 V AC 50/60 Hz || 75-75 kW 500 V AC 50/60 Hz || 75-75 kW 660...690 V AC 50/60 Hz || 90-90 kW 660...6
- Breaking Capacity:
- 50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 35 kA 208Y/120 V AC 50/60 Hz UL 60947 || 35 kA 240 V AC 50/60 Hz U
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 116 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Rohs Exemption Information:
- Yes
- Trip Unit Technology:
- electronic || thermal-magnetic
- Ambient Air Temperature For Storage:
- -50-85°C
- Mercury Free:
- Yes
- Product Name:
- TeSys GV4 || TeSys Deca
- Ik Degree Of Protection:
- IK07 IEC 62262
- Width:
- 81 mm
- Product Certifications:
- IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 800 V AC 50/60 Hz IEC 60947-2
- Climatic Withstand:
- IACS E10
- Line Rated Current:
- 115 A
- Device Short Name:
- GV4PE
- Power Dissipation Per Pole:
- 4.6 W
- Ambient Air Temperature For Operation:
- -25-70°C
- [Ith] Conventional Free Air Thermal Current:
- 115 A IEC 60947-4-1
- Poles Description:
- 3P
- Tightening Torque:
- 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
- Mechanical Robustness:
- vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
- Operating Altitude:
- 5000 m
- Phase Failure Sensitivity:
- yes IEC 60947-4-1
- Pvc Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.