Schneider Electric GV4PE12S Motor circuit breaker, TeSys GV4, 3P, 12.5A, Icu 100kA, thermal magnetic, Everlink terminals
Schneider Electric
$845.00
TeSys GV motor circuit breaker, 3 poles (3P), 12.5A/690V, for protection of 3-phase motors 3-5.5kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 5-12.5A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
- Depth:
- 116 mm
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-2
- Climatic Withstand:
- IACS E10
- Net Weight:
- 1.45 kg
- Rated Duty:
- continuous IEC 60947-4-1
- Motor Power Kw:
- 3-3 kW 400...415 V AC 50/60 Hz || 3-3 kW 500 V AC 50/60 Hz || 4-4 kW 500 V AC 50/60 Hz || 5.5-5.5 kW 660...690 V AC 50/60 Hz || 7.5-7.5 kW 660...690 V AC 50/60 Hz || 4-4 kW 400...415 V AC 50/60 Hz || 5.5-5.5 kW 400...415 V AC 50/60 Hz || 5.5-5.5 kW 5
- Weight:
- 1.45 kg
- Color:
- Gray RAL 7016)
- Mechanical Robustness:
- vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
- Ip Degree Of Protection:
- IP40 IEC 60529
- Fire Resistance:
- 960°C IEC 60695-2-11
- Magnetic Tripping Current:
- 212-212 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- TeSys Deca
- Pollution Degree:
- 3
- Halogen Content Performance:
- Halogen free plastic parts product
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Control Type:
- toggle
- Sustainable Offer Status:
- Green Premium product
- [Ith] Conventional Free Air Thermal Current:
- 115 A IEC 60947-4-1
- Product Or Component Type:
- motor circuit breaker
- Range Of Product:
- TeSys GV4
- Trip Unit Technology:
- electronic || thermal-magnetic
- Mechanical Durability:
- 40000 cycles
- Tightening Torque:
- 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
- Warranty:
- 18 months
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Operating Position:
- any position
- Poles Description:
- 3P
- Suitability For Isolation:
- yes IEC 60947-1
- Ik Degree Of Protection:
- IK07 IEC 62262
- Ambient Air Temperature For Operation:
- -25-70°C
- Breaking Capacity:
- 120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 208Y/120 V AC
- Environmental Disclosure:
- ENVPEP1704004EN
- Device Short Name:
- GV4PE
- Circularity Profile:
- ENVEOLI1704004EN
- Power Dissipation Per Pole:
- 4.6 W
- Operating Altitude:
- 5000 m
- Connections - Terminals:
- EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Product Certifications:
- IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
- Ambient Air Temperature For Storage:
- -50-85°C
- Device Application:
- motor protection
- Standards:
- CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
- Product Name:
- TeSys GV4 || TeSys Deca