Schneider Electric

Schneider Electric GV4PE80N Motor circuit breaker, TeSys GV4, 3P, 80A, Icu 50kA, thermal magnetic, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4PE80N
MPN:
GV4PE80N
Condition:
New
Ambient Air Temperature For Storage:
-50-85°C
Poles Description:
3P
Pollution Degree:
3
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Eu Rohs Directive:
Compliant with Exemptions
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Breaking Capacity:
100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 65 kA 208Y/120 V AC 50/60 Hz UL 60947 || 65 kA 240 V AC 50/60 Hz
Fire Resistance:
960°C IEC 60695-2-11
Product Name:
TeSys GV4 || TeSys Deca
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Climatic Withstand:
IACS E10
Device Application:
motor protection
Sustainable Offer Status:
Green Premium product
Color:
Gray RAL 7016)
Control Type:
toggle
Ambient Air Temperature For Operation:
-25-70°C
Motor Power Kw:
37-37 kW 400...415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 22-22 kW 400...415 V AC 50/60 Hz || 30-30 kW 500 V AC 50/60 Hz || 37-37 kW 660...690 V AC 50/60 Hz || 45-45 kW 660...690 V AC 50/60 Hz || 55-55 kW 660...690 V AC 50/60 Hz || 30-30 kW 4
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Power Dissipation Per Pole:
4.6 W
Weight:
1.45 kg
Net Weight:
1.45 kg
Mechanical Durability:
40000 cycles
Product Or Component Type:
motor circuit breaker
Environmental Disclosure:
ENVPEP1704004EN
Phase Failure Sensitivity:
yes IEC 60947-4-1
Circularity Profile:
ENVEOLI1704004EN
Line Rated Current:
80 A
Electrical Durability:
14000 cycles AC-3 440 V In/2 || 7000 cycles AC-3 440 V In
Trip Unit Technology:
thermal-magnetic || electronic
Operating Altitude:
5000 m
Rohs Exemption Information:
Yes
Halogen Content Performance:
Halogen free plastic parts product
Operating Position:
any position
Range Of Product:
TeSys GV4
Warranty:
18 months
Standards:
CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Depth:
116 mm
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Height:
155 mm
Device Short Name:
GV4PE
Country of Origin:
Poland
Ik Degree Of Protection:
IK07 IEC 62262
$795.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 80A/690V, for protection of 3-phase motors 22-37kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 40-80A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).