Schneider Electric

Schneider Electric GV4PEM03N Motor circuit breaker, TeSys GV4, 3P, 3.5A, Icu 50kA, thermal magnetic multifunction, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4PEM03N
MPN:
GV4PEM03N
Condition:
New
Motor Power Kw:
0.55-0.55 kW 400...415 V AC 50/60 Hz || 0.75-0.75 kW 400...415 V AC 50/60 Hz || 0.75-0.75 kW 500 V AC 50/60 Hz || 1.1-1.1 kW 500 V AC 50/60 Hz || 1.1-1.1 kW 660...690 V AC 50/60 Hz || 1.5-1.5 kW 660...690 V AC 50/60 Hz || 1.5-1.5 kW 500 V AC 50/60 Hz
Magnetic Tripping Current:
59-59 A
Net Weight:
1.45 kg
Mechanical Durability:
40000 cycles
Power Dissipation Per Pole:
4.6 W
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Maximum Operating Rate:
25 cyc/h
Device Short Name:
GV4PEM
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Product Name:
TeSys GV4 || TeSys Deca
Ik Degree Of Protection:
IK07 IEC 62262
Product Or Component Type:
motor circuit breaker
Warranty:
18 months
Color:
Gray RAL 7016)
Circularity Profile:
ENVEOLI1704004EN
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Poles Description:
3P
Range Of Product:
TeSys GV4
Range:
TeSys Deca
Halogen Content Performance:
Halogen free plastic parts product
Weight:
1.45 kg
Pollution Degree:
3
Climatic Withstand:
IACS E10
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
116 mm
Ambient Air Temperature For Storage:
-50-85°C
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mercury Free:
Yes
Sustainable Offer Status:
Green Premium product
Phase Failure Sensitivity:
yes IEC 60947-4-1
Country of Origin:
Poland
Ambient Air Temperature For Operation:
-25-70°C
Pvc Free:
Yes
Control Type:
toggle
Ip Degree Of Protection:
IP40 IEC 60529
Trip Unit Technology:
thermal-magnetic || electronic
Breaking Capacity:
100 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 65 kA 208Y/120 V AC 50/60 Hz UL 60947 || 65 kA 240 V AC 50/60 Hz
Rated Duty:
continuous IEC 60947-4-1
Eu Rohs Directive:
Compliant with Exemptions
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Fire Resistance:
960°C IEC 60695-2-11
Rohs Exemption Information:
Yes
$1,267.50

Description

TeSys GV motor circuit breaker, 3 poles (3P), 3.5A/690V, for protection of 3-phase motors 0.55-1.5kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 1.4-3.5A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose