Schneider Electric

Schneider Electric GV4PEM115S Motor circuit breaker, TeSys GV4, 3P, 115A, Icu 100kA, thermal magnetic multifunction, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4PEM115S
MPN:
GV4PEM115S
Condition:
New
Product Name:
TeSys GV4 || TeSys Deca
Motor Power Kw:
37-37 kW 400...415 V AC 50/60 Hz || 45-45 kW 400...415 V AC 50/60 Hz || 55-55 kW 400...415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 55-55 kW 500 V AC 50/60 Hz || 75-75 kW 500 V AC 50/60 Hz || 75-75 kW 660...690 V AC 50/60 Hz || 90-90 kW 660...6
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Range:
TeSys Deca
Sustainable Offer Status:
Green Premium product
Operating Altitude:
5000 m
Breaking Capacity:
120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 208Y/120 V AC
Mechanical Durability:
40000 cycles
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Power Dissipation Per Pole:
4.6 W
Ip Degree Of Protection:
IP40 IEC 60529
Poles Description:
3P
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Pvc Free:
Yes
Ik Degree Of Protection:
IK07 IEC 62262
Fire Resistance:
960°C IEC 60695-2-11
Weight:
1.45 kg
Environmental Disclosure:
ENVPEP1704004EN
Mercury Free:
Yes
Maximum Operating Rate:
25 cyc/h
Line Rated Current:
115 A
Ambient Air Temperature For Storage:
-50-85°C
Color:
Gray RAL 7016)
Product Or Component Type:
motor circuit breaker
Control Type:
toggle
Ambient Air Temperature For Operation:
-25-70°C
Standards:
CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Device Application:
motor protection
Circularity Profile:
ENVEOLI1704004EN
Range Of Product:
TeSys GV4
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Magnetic Tripping Current:
1955-1955 A
Warranty:
18 months
Halogen Content Performance:
Halogen free plastic parts product
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Rohs Exemption Information:
Yes
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Climatic Withstand:
IACS E10
Trip Unit Technology:
thermal-magnetic || electronic
Country of Origin:
Mexico
Operating Position:
any position
Electrical Durability:
10000 cycles AC-3 440 V In/2 || 5000 cycles AC-3 440 V In
Device Short Name:
GV4PEM
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
$1,095.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose