Schneider Electric

Schneider Electric HDA260303 Circuit breaker, PowerPacT H, 30A, 2 pole, 600VAC, 14kA, I-Line, thermal magnetic, 80%, BA

(No reviews yet) Write a Review
SKU:
HDA260303
MPN:
HDA260303
Condition:
New
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Control Type:
toggle
Wire Stripping Length:
16 mm
Protected Poles Description:
2t
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Network Frequency:
50/60 Hz
Country of Origin:
United States
Trip Unit Technology:
thermal-magnetic
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Weight:
2.2 kg
Mounting Height:
3 in
Range:
PowerPact
Eu Rohs Directive:
Compliant with Exemptions
Communication Interface:
Modbus || Ethernet
Mounting Support:
bracket
Circularity Profile:
ENVEOLI2206027EN
Electrical Connection:
I-Line connection, line || lugs, load
Product Certifications:
UL || CSA || NOM
Length:
16 mm
Utilisation Category:
category A
Quantity Per Set:
1
Environmental Disclosure:
ENVPEP2206027EN
Product Or Component Type:
circuit breaker
Breaking Capacity Code:
D
Magnetic Hold Current:
350 A
Depth:
86 mm
Circuit Breaker Application:
HACR rated
Magnetic Tripping Current:
750-750 A
Height:
3 in
Quality Labels:
CE
Rohs Exemption Information:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Height:
163 mm
Suitability For Isolation:
yes IEC 60947-2
Line Rated Current:
30-30 A
Ambient Air Temperature For Storage:
-50-85°C
Warranty:
18 months
Net Weight:
2.2 kg
Device Application:
distribution
Width:
104 mm
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Pollution Degree:
3 IEC 60947-1
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Ambient Air Temperature For Operation:
-25-70°C
Local Signaling:
switched off (OFF) 1 trip indicator green)
Sustainable Offer Status:
Green Premium product
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
$1,348.50

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 30A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a BA phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose