Schneider Electric

Schneider Electric HDA260806 Circuit breaker, PowerPacT H, 80A, 2 pole, 600VAC, 14kA, I-Line, thermal magnetic, 80%, CB

(No reviews yet) Write a Review
SKU:
HDA260806
MPN:
HDA260806
Condition:
New
Sustainable Offer Status:
Green Premium product
Mounting Support:
bracket
Local Signaling:
switched off (OFF) 1 trip indicator green)
Phase Connection:
CB
Product Name:
PowerPact H
Electrical Connection:
I-Line connection, line || lugs, load
Ambient Air Temperature For Operation:
-25-70°C
Quantity Per Set:
1
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Magnetic Hold Current:
800 A
Height:
3 in
Quality Labels:
CE
Product Certifications:
UL || CSA || NOM
Warranty:
18 months
Communication Interface:
Modbus || Ethernet
Ip Degree Of Protection:
front cover IP40 IEC 60529
Pollution Degree:
3 IEC 60947-1
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Net Weight:
2.2 kg
Eu Rohs Directive:
Compliant with Exemptions
Country of Origin:
United States
Ambient Air Temperature For Storage:
-50-85°C
Continuous Current Rating:
0.8
Rohs Exemption Information:
Yes
Control Type:
toggle
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Utilisation Category:
category A
Color:
Black
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Suitability For Isolation:
yes IEC 60947-2
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Device Application:
distribution
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Circularity Profile:
ENVEOLI2206027EN
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Terminal Identifier:
AL150HD
Breaking Capacity Code:
D
Weight:
2.2 kg
Mounting Mode:
I-Line bracket)
Circuit Breaker Application:
HACR rated
Mounting Height:
3 in
Product Or Component Type:
circuit breaker
Mercury Free:
Yes
Protected Poles Description:
2t
Line Rated Current:
80-80 A
$1,632.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 80A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a CB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose