Schneider Electric

Schneider Electric HDA260901 Circuit breaker, PowerPacT H, 90A, 2 pole, 600VAC, 14kA, I-Line, thermal magnetic, 80%, AB

(No reviews yet) Write a Review
SKU:
HDA260901
MPN:
HDA260901
Condition:
New
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Length:
16 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Communication Interface:
Modbus || Ethernet
Pvc Free:
Yes
Electrical Connection:
I-Line connection, line || lugs, load
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Breaking Capacity Code:
D
Wire Stripping Length:
16 mm
Product Name:
PowerPact H
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Continuous Current Rating:
0.8
Product Certifications:
UL || CSA || NOM
Pollution Degree:
3 IEC 60947-1
Quality Labels:
CE
Weight:
2.2 kg
Warranty:
18 months
Poles Description:
2P
Height:
163 mm
Circuit Breaker Application:
HACR rated
Eu Rohs Directive:
Compliant
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Mounting Support:
bracket
Mounting Height:
3 in
Magnetic Tripping Current:
1450-1450 A
Ambient Air Temperature For Storage:
-50-85°C
Ip Degree Of Protection:
front cover IP40 IEC 60529
Environmental Disclosure:
ENVPEP1311006EN
Quantity Per Set:
1
Trip Unit Technology:
thermal-magnetic
Color:
Black
Protected Poles Description:
2t
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Country of Origin:
United States
Phase Connection:
AB
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Line Rated Current:
90-90 A
Net Weight:
2.2 kg
Mounting Mode:
I-Line bracket)
Circularity Profile:
ENVEOLI1311006EN
Local Signaling:
switched off (OFF) 1 trip indicator green)
Device Application:
distribution
Magnetic Hold Current:
800 A
Width:
104 mm
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Range:
PowerPact
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Height:
3 in
$2,448.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 90A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose