Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Mounting Height:
4.5 in
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
front cover IP40 IEC 60529
Circuit Breaker Application:
HACR rated
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Continuous Current Rating:
0.8
Electrical Connection:
I-Line connection, line || lugs, load
Breaking Capacity Code:
D
Magnetic Hold Current:
400 A
Color:
Black
Quantity Per Set:
1
Poles Description:
3P
Sustainable Offer Status:
Green Premium product
Device Application:
distribution
Protected Poles Description:
3t
Local Signaling:
switched off (OFF) 1 trip indicator green)
Height:
163 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Mercury Free:
Yes
Range:
PowerPact
Magnetic Tripping Current:
850-850 A
Quality Labels:
CE
Mounting Mode:
I-Line bracket)
Mounting Support:
bracket
Utilisation Category:
category A
Warranty:
18 months
Pvc Free:
Yes
Net Weight:
2.2 kg
Line Rated Current:
40-40 A
Circularity Profile:
ENVEOLI2206027EN
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Network Frequency:
50/60 Hz
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Environmental Disclosure:
ENVPEP2206027EN
Height:
4.5 in
Suitability For Isolation:
yes IEC 60947-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Rohs Exemption Information:
Yes
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Length:
16 mm
Country of Origin:
United States
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Product Or Component Type:
circuit breaker
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ambient Air Temperature For Operation:
-25-70°C
$1,686.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 40A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a CBA phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.