Schneider Electric

Schneider Electric HDA36060U53X Circuit breaker, PowerPacT H, 60A, 3 pole, 600VAC, 14kA, I-Line, Micrologic 5.2E, 80%, ABC

(No reviews yet) Write a Review
SKU:
HDA36060U53X
MPN:
HDA36060U53X
Condition:
New
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Device Application:
distribution
Height:
163 mm
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Continuous Current Rating:
0.8
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Height:
4.5 in
Product Or Component Type:
circuit breaker
Quality Labels:
CE
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Country of Origin:
United States
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Poles Description:
3P
Ambient Air Temperature For Storage:
-50-85°C
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Color:
Black
Terminal Identifier:
AL150HD
Utilisation Category:
category A
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Communication Interface:
Modbus || Ethernet
Ambient Air Temperature For Operation:
-25-70°C
Wire Stripping Length:
16 mm
Product Name:
PowerPact H
Product Certifications:
UL || CSA || NOM
Electrical Connection:
I-Line connection, line || lugs, load
Suitability For Isolation:
yes IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Eu Rohs Directive:
Compliant with Exemptions
Environmental Disclosure:
ENVPEP2206028EN
Circularity Profile:
ENVEOLI2206028EN
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Phase Connection:
ABC
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Range:
PowerPact
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Length:
16 mm
Net Weight:
2.2 kg
Trip Unit Name:
MicroLogic 5.2 E
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Network Frequency:
50/60 Hz
Protected Poles Description:
3t
Depth:
86 mm
Trip Unit Technology:
electronic, energy, MicroLogic 5.2 E, LSI
Mounting Mode:
I-Line bracket)
Circuit Breaker Application:
HACR rated
Mounting Support:
bracket
Breaking Capacity Code:
D
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Pvc Free:
Yes
Quantity Per Set:
1
$2,523.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Energy with a 5.2E trip unit and an LSI function with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 60A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.