Schneider Electric

Schneider Electric HDL36150U54X Circuit breaker, PowerPacT H, 150A, 3 pole, 600VAC, 14kA, lugs, Micrologic 6.2E, 80%

(No reviews yet) Write a Review
SKU:
HDL36150U54X
MPN:
HDL36150U54X
Condition:
New
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Country of Origin:
United States
Utilisation Category:
category A
Continuous Current Rating:
0.8
Length:
16 mm
Eu Rohs Directive:
Compliant with Exemptions
Product Name:
PowerPact H
Poles Description:
3P
Ambient Air Temperature For Storage:
-50-85°C
Sustainable Offer Status:
Green Premium product
Line Rated Current:
150-150 A
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Breaking Capacity Code:
D
Product Or Component Type:
circuit breaker
Suitability For Isolation:
yes IEC 60947-2
Weight:
2.2 kg
Circularity Profile:
ENVEOLI2206028EN
Ambient Air Temperature For Operation:
-25-70°C
Net Weight:
2.2 kg
Electrical Connection:
lugs, line || lugs, load
Range:
PowerPact
Color:
Black
Mercury Free:
Yes
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Warranty:
18 months
Mounting Mode:
unit mount lug)
Quantity Per Set:
1
Device Application:
distribution
Product Certifications:
UL || CSA || NOM
Communication Interface:
Modbus || Ethernet
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Trip Unit Name:
MicroLogic 6.2 E
Width:
104 mm
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Ip Degree Of Protection:
front cover IP40 IEC 60529
Circuit Breaker Application:
HACR rated
Terminal Identifier:
AL150HD
Control Type:
toggle
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Network Frequency:
50/60 Hz
Protected Poles Description:
3t
Trip Unit Technology:
electronic, energy, MicroLogic 6.2 E, LSIG
$4,623.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Energy with a 6.2E trip unit and an LSIG function with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose