Schneider Electric

Schneider Electric HGA36060U43X Circuit breaker, PowerPacT H, 60A, 3 pole, 600VAC, 18kA, I-Line, Micrologic 5.2A, 80%, ABC

(No reviews yet) Write a Review
SKU:
HGA36060U43X
MPN:
HGA36060U43X
Condition:
New
Depth:
86 mm
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Mounting Height:
4.5 in
Ambient Air Temperature For Operation:
-25-70°C
Wire Stripping Length:
16 mm
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Utilisation Category:
category A
Mercury Free:
Yes
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Quality Labels:
CE
Product Or Component Type:
circuit breaker
Height:
163 mm
Eu Rohs Directive:
Compliant with Exemptions
Electrical Connection:
I-Line connection, line || lugs, load
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Net Weight:
2.2 kg
Circularity Profile:
ENVEOLI2206028EN
Continuous Current Rating:
0.8
Range:
PowerPact
Mounting Support:
bracket
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Environmental Disclosure:
ENVPEP2206028EN
Network Frequency:
50/60 Hz
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Poles Description:
3P
Pollution Degree:
3 IEC 60947-1
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Sustainable Offer Status:
Green Premium product
Terminal Identifier:
AL150HD
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Product Name:
PowerPact H
Ip Degree Of Protection:
front cover IP40 IEC 60529
Ambient Air Temperature For Storage:
-50-85°C
Trip Unit Technology:
electronic, ammeter, MicroLogic 5.2 A, LSI
Protected Poles Description:
3t
Breaking Capacity Code:
G
Height:
4.5 in
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Control Type:
toggle
Suitability For Isolation:
yes IEC 60947-2
Mounting Mode:
I-Line bracket)
Circuit Breaker Application:
HACR rated
Communication Interface:
Modbus || Ethernet
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Device Application:
distribution
Pvc Free:
Yes
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Quantity Per Set:
1
$2,570.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Ammeter with a 5.2A trip unit and an LSI function with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 60A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose