- Mounting Mode:
- unit mount lug)
- Ambient Air Temperature For Storage:
- -50-85°C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Environmental Disclosure:
- ENVPEP2206028EN
- Color:
- Black
- Circularity Profile:
- ENVEOLI2206028EN
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Poles Description:
- 3P
- Trip Unit Name:
- MicroLogic 5.2 A
- Weight:
- 2.2 kg
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Protected Poles Description:
- 3t
- Product Name:
- PowerPact H
- Rohs Exemption Information:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- lug
- Circuit Breaker Application:
- HACR rated
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Communication Interface:
- Modbus || Ethernet
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Line Rated Current:
- 100-100 A
- Warranty:
- 18 months
- Breaking Capacity Code:
- G
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Eu Rohs Directive:
- Compliant with Exemptions
- Continuous Current Rating:
- 1
- Length:
- 16 mm
- Quality Labels:
- CE
- Control Type:
- toggle
- Electrical Connection:
- lugs, line || lugs, load
- Suitability For Isolation:
- yes IEC 60947-2
- Width:
- 104 mm
- Terminal Identifier:
- AL150HD
- Pollution Degree:
- 3 IEC 60947-1
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Quantity Per Set:
- 1
- Range:
- PowerPact
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Net Weight:
- 2.2 kg
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.2 A, LSI
- Mercury Free:
- Yes
- Device Application:
- distribution