Schneider Electric

Schneider Electric HGL36150CU44X Circuit breaker, PowerPacT H, 150A, 3 pole, 600VAC, 18kA, lugs, Micrologic 6.2A, 100%

(No reviews yet) Write a Review
SKU:
HGL36150CU44X
MPN:
HGL36150CU44X
Condition:
New
Terminal Identifier:
AL150HD
Quantity Per Set:
1
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Trip Unit Name:
MicroLogic 6.2 A
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Network Frequency:
50/60 Hz
Net Weight:
2.2 kg
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ip Degree Of Protection:
front cover IP40 IEC 60529
Range:
PowerPact
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Ambient Air Temperature For Storage:
-50-85°C
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Color:
Black
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Circuit Breaker Application:
HACR rated
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Rohs Exemption Information:
Yes
Ambient Air Temperature For Operation:
-25-70°C
Sustainable Offer Status:
Green Premium product
Product Name:
PowerPact H
Weight:
2.2 kg
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Trip Unit Technology:
electronic, ammeter, MicroLogic 6.2 A, LSIG
Mounting Support:
lug
Continuous Current Rating:
1
Circularity Profile:
ENVEOLI2206028EN
Device Application:
distribution
Poles Description:
3P
Country of Origin:
United States
Wire Stripping Length:
16 mm
Mounting Mode:
unit mount lug)
Depth:
86 mm
Electrical Connection:
lugs, line || lugs, load
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Protected Poles Description:
3t
Control Type:
toggle
Eu Rohs Directive:
Compliant with Exemptions
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Environmental Disclosure:
ENVPEP2206028EN
Communication Interface:
Modbus || Ethernet
Utilisation Category:
category A
$5,890.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Ammeter with a 6.2A trip unit and an LSIG function with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose