- Product Or Component Type:
- circuit breaker
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Ambient Air Temperature For Operation:
- -25-70°C
- Environmental Disclosure:
- ENVPEP1311006EN
- Circuit Breaker Application:
- HACR rated
- Wire Stripping Length:
- 16 mm
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Suitability For Isolation:
- yes IEC 60947-2
- Country of Origin:
- United States
- Control Type:
- toggle
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Rohs Exemption Information:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ambient Air Temperature For Storage:
- -50-85°C
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Pollution Degree:
- 3 IEC 60947-1
- Net Weight:
- 2.2 kg
- Eu Rohs Directive:
- Compliant
- Protected Poles Description:
- 3t
- Color:
- Black
- Continuous Current Rating:
- 0.8
- Circularity Profile:
- ENVEOLI1311006EN
- Poles Description:
- 3P
- Network Frequency:
- 50/60 Hz
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Utilisation Category:
- category A
- Quantity Per Set:
- 1
- Range:
- PowerPact
- Line Rated Current:
- 30-30 A
- Product Name:
- PowerPact H
- Sustainable Offer Status:
- Green Premium product
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Certifications:
- UL || CSA || NOM
- Trip Unit Technology:
- thermal-magnetic
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Magnetic Hold Current:
- 350 A
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Depth:
- 86 mm
- Magnetic Tripping Current:
- 750-750 A
- Mercury Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Terminal Identifier:
- AL150HD