- Continuous Current Rating:
- 0.8
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Circularity Profile:
- ENVEOLI2206028EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Control Type:
- toggle
- Country of Origin:
- United States
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Range:
- PowerPact
- Line Rated Current:
- 100-100 A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Length:
- 16 mm
- Net Weight:
- 2.2 kg
- Protected Poles Description:
- 3t
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Quantity Per Set:
- 1
- Depth:
- 86 mm
- Mounting Support:
- lug
- Breaking Capacity Code:
- G
- Wire Stripping Length:
- 16 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Quality Labels:
- CE
- Width:
- 104 mm
- Utilisation Category:
- category A
- Magnetic Hold Current:
- 900 A
- Trip Unit Name:
- MicroLogic 6.2 A
- Mercury Free:
- Yes
- Magnetic Tripping Current:
- 1700-1700 A
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Storage:
- -50-85°C
- Poles Description:
- 3P
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Height:
- 163 mm
- Product Certifications:
- UL || CSA || NOM
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Operation:
- -25-70°C
- Product Or Component Type:
- circuit breaker
- Pvc Free:
- Yes
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.2 A, LSIG
- Product Name:
- PowerPact H
- Device Application:
- distribution
- Pollution Degree:
- 3 IEC 60947-1
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Mode:
- unit mount lug)
- Terminal Identifier:
- AL150HD