Schneider Electric

Schneider Electric HJL36025SA Circuit breaker, PowerPacT H, 25A, 3 pole, 600VAC, 25kA, lugs, thermal magnetic, 80%, shunt

(No reviews yet) Write a Review
SKU:
HJL36025SA
MPN:
HJL36025SA
Condition:
New
Local Signaling:
switched off (OFF) 1 trip indicator green)
Weight:
2.2 kg
Pollution Degree:
3 IEC 60947-1
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Product Certifications:
UL || CSA || NOM
Electrical Connection:
lugs, line || lugs, load
Magnetic Tripping Current:
750-750 A
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Continuous Current Rating:
0.8
Ambient Air Temperature For Operation:
-25-70°C
Rohs Exemption Information:
Yes
Device Application:
distribution
Terminal Identifier:
AL150HD
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Warranty:
18 months
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Trip Unit Technology:
thermal-magnetic
Accessory / Separate Part Type:
shunt trip 110...130 V AC compartment
Wire Stripping Length:
16 mm
Network Frequency:
50/60 Hz
Suitability For Isolation:
yes IEC 60947-2
Product Name:
PowerPact H
Circularity Profile:
ENVEOLI2206027EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Poles Description:
3P
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Net Weight:
2.2 kg
Communication Interface:
Modbus || Ethernet
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Breaking Capacity Code:
J
Circuit Breaker Application:
HACR rated
Length:
16 mm
Sustainable Offer Status:
Green Premium product
Color:
Black
Quantity Per Set:
1
Quality Labels:
CE
Line Rated Current:
25-25 A
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Control Type:
toggle
Mounting Support:
lug
Height:
163 mm
Pvc Free:
Yes
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Utilisation Category:
category A
Ip Degree Of Protection:
front cover IP40 IEC 60529
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Magnetic Hold Current:
350 A
$2,666.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 25A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a factory installed 120VAC shunt trip. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.