Schneider Electric

Schneider Electric HJL36050M72AB Motor circuit protector, PowerPacT H, 50A, 3 pole, 600VAC, 25kA, lugs, thermal magnetic, 80%, aux switch

(No reviews yet) Write a Review
SKU:
HJL36050M72AB
MPN:
HJL36050M72AB
Condition:
New
Poles Description:
3P
Eu Rohs Directive:
Compliant with Exemptions
Ambient Air Temperature For Operation:
-25-70°C
Net Weight:
2.2 kg
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mercury Free:
Yes
Utilisation Category:
category A
Product Or Component Type:
Motor Circuit Protector
Mounting Support:
lug
Communication Interface:
Modbus || Ethernet
Quality Labels:
CE
Depth:
86 mm
Ip Degree Of Protection:
front cover IP40 IEC 60529
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Environmental Disclosure:
ENVPEP2206027EN
Device Application:
distribution
Continuous Current Rating:
0.8
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Line Rated Current:
50-50 A
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Network Frequency:
50/60 Hz
Control Type:
toggle
Mounting Mode:
unit mount lug)
Color:
Black
Protected Poles Description:
3t
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Rohs Exemption Information:
Yes
Pvc Free:
Yes
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Magnetic Tripping Current:
84-546 A
Breaking Capacity Code:
J
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Terminal Identifier:
AL150HD
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Electrical Connection:
lugs, line || lugs, load
Wire Stripping Length:
16 mm
Ambient Air Temperature For Storage:
-50-85°C
Product Certifications:
UL || CSA || NOM
Sustainable Offer Status:
Green Premium product
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Accessory / Separate Part Type:
auxiliary switch 24 V AC/DC 2 NO + 2 NC cover frame
[Ith] Conventional Free Air Thermal Current:
14-42 A
Trip Unit Technology:
thermal-magnetic
$1,979.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 50A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a factory installed 2A/2B auxiliary switch. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.