Schneider Electric HL2IMA16C1 Surge protection device, Surgelogic, HL, 160kA, 208Y/120VAC, 3 phase, 4 wire, SPD type 1
Schneider Electric
$10,872.00
Surgelogic™ internally mounted surge protection devices delivers specification grade performance for service entrance or critical branch I-Line panel applications. These multiphase systems provide suppression, enchanced EFI/RFI filtering for all critical modes inside electrical equipment, and shorter lead lengths with superior SPD performance. They provide better performance with a diagnostic interface with push to test diagnostic switches, red and green status LEDs, module status LEDs per mode, dry contacts, audible alarm with disable switch, and a surge counter. These products have a 10 year product warranty and 10 modes of protection. This surge protection device is 3 phase, 4-wire + ground, 208Y/277 V, 50 kA breaking capacity, 160 kA surge current, and short circuit current rating of 200 kA. The device is engineered to UL 489 11th Edition, type 2 SPD and complies with UL 96A 12th Edition Master Label for Lightning Protection Systems.
- Country of Origin:
- Mexico
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity Code:
- HL
- [Uc] Maximum Continuous Operating Voltage:
- 150 V
- Cable Length:
- 483 mm
- Local Signaling:
- status LED green per phase normal operation || status LED red per phase fault
- Length:
- 483 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Nema Degree Of Protection:
- NEMA 1
- Trip Unit Technology:
- thermal-magnetic
- Phase:
- 3 phase
- [Ue] Rated Operational Voltage:
- 208Y/120 V AC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Number Of Poles:
- 3
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Line Rated Current:
- 60 A
- Surge Current:
- 160 kA
- Wiring Configuration:
- 4-wire
- Rohs Exemption Information:
- Yes
- Short-Circuit Protection:
- 200 kA
- Provided Equipment:
- alarm enable/disable switch || surge counter || circuit-breaker
- Range Of Product:
- Surgelogic
- Depth:
- 142.1 mm
- Connections - Terminals:
- I-Line line || lugs ground AWG 6 copper 4 N.m || lugs neutral AWG 6 copper 4 N.m
- Mounting Support:
- panel mounting
- Standards:
- UL 1449:ed. 3 || CSA C22.2 No 8:1986 || UL 96A:ed. 12 || UL 489:ed. 11 || CSA C22.2 No 5-09
- Product Or Component Type:
- surge protection device
- Device Short Name:
- IMA
- Breaking Capacity:
- 50 kA