Schneider Electric HLA261001 Circuit breaker, PowerPacT H, 100A, 2 pole, 600VAC, 50kA, I-Line, thermal magnetic, 80%, AB
Schneider Electric
$4,036.50
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 50kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 100A, 2 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Height:
- 4.5 in
- Quality Labels:
- CE
- Weight:
- 2.2 kg
- Line Rated Current:
- 100-100 A
- Mounting Height:
- 4.5 in
- Wire Stripping Length:
- 16 mm
- Poles Description:
- 2P
- Rohs Exemption Information:
- Yes
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Circularity Profile:
- ENVEOLI2206027EN
- Pvc Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Height:
- 163 mm
- Phase Connection:
- AB
- Eu Rohs Directive:
- Compliant with Exemptions
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity Code:
- L
- Length:
- 16 mm
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Quantity Per Set:
- 1
- Ambient Air Temperature For Operation:
- -25-70°C
- Trip Unit Technology:
- thermal-magnetic
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mounting Support:
- bracket
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Control Type:
- toggle
- Sustainable Offer Status:
- Green Premium product
- Mercury Free:
- Yes
- Utilisation Category:
- category A
- Continuous Current Rating:
- 0.8
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Net Weight:
- 2.2 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Depth:
- 86 mm
- Terminal Identifier:
- AL150HD
- Country of Origin:
- United States
- Device Application:
- distribution
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Magnetic Tripping Current:
- 1700-1700 A
- Communication Interface:
- Modbus || Ethernet
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Storage:
- -50-85°C
- Circuit Breaker Application:
- HACR rated
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- [Ics] Rated Service Breaking Capacity: