Schneider Electric

Schneider Electric HLL26060 Circuit breaker, PowerPacT H, 60A, 2 pole, 600VAC, 50kA, lugs, thermal magnetic, 80%

(No reviews yet) Write a Review
SKU:
HLL26060
MPN:
HLL26060
Condition:
New
Circularity Profile:
ENVEOLI2206027EN
Environmental Disclosure:
ENVPEP2206027EN
Sustainable Offer Status:
Green Premium product
Electrical Connection:
lugs, line || lugs, load
[Ics] Rated Service Breaking Capacity:
125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Communication Interface:
Modbus || Ethernet
Local Signaling:
switched off (OFF) 1 trip indicator green)
Protected Poles Description:
2t
Ambient Air Temperature For Operation:
-25-70°C
Quantity Per Set:
1
Suitability For Isolation:
yes IEC 60947-2
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Device Application:
distribution
Pvc Free:
Yes
Magnetic Tripping Current:
1450-1450 A
Magnetic Hold Current:
800 A
Range:
PowerPact
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Ip Degree Of Protection:
front cover IP40 IEC 60529
Circuit Breaker Application:
HACR rated
Eu Rohs Directive:
Compliant with Exemptions
Rohs Exemption Information:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mounting Mode:
unit mount lug)
Line Rated Current:
60-60 A
Trip Unit Technology:
thermal-magnetic
Pollution Degree:
3 IEC 60947-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Net Weight:
2.2 kg
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Weight:
2.2 kg
Network Frequency:
50/60 Hz
Terminal Identifier:
AL150HD
Product Name:
PowerPact H
Wire Stripping Length:
16 mm
Continuous Current Rating:
0.8
Utilisation Category:
category A
Warranty:
18 months
Length:
16 mm
Depth:
86 mm
Color:
Black
$3,546.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 50kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 60A, 2 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.