- Mounting Mode:
- unit mount lug)
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Protected Poles Description:
- 3t
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Weight:
- 2.2 kg
- Suitability For Isolation:
- yes IEC 60947-2
- Depth:
- 86 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Color:
- Black
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Country of Origin:
- United States
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Poles Description:
- 3P
- Circuit Breaker Application:
- HACR rated
- Device Application:
- distribution
- Quantity Per Set:
- 1
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- lug
- Line Rated Current:
- 60-60 A
- Quality Labels:
- CE
- Circularity Profile:
- ENVEOLI2206028EN
- Continuous Current Rating:
- 0.8
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Mercury Free:
- Yes
- Control Type:
- toggle
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Product Name:
- PowerPact H
- Range:
- PowerPact
- Product Certifications:
- UL || CSA || NOM
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Network Frequency:
- 50/60 Hz
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -25-70°C
- Product Or Component Type:
- circuit breaker
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Wire Stripping Length:
- 16 mm
- Length:
- 16 mm
- Pvc Free:
- Yes
- Terminal Identifier:
- AL150HD
- Ambient Air Temperature For Storage:
- -50-85°C
- Trip Unit Name:
- MicroLogic 3.2 S