Schneider Electric

Schneider Electric HOM3060M125PC Load center, Homeline, 1 phase, 30 spaces, 60 circuits, 125A convertible main breaker, PoN, NEMA1, combo cover

(No reviews yet) Write a Review
SKU:
HOM3060M125PC
MPN:
HOM3060M125PC
Condition:
New
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Phase:
1 phase 3 wires
Box Number:
10
Provided Equipment:
circuit-breaker 1 ) 2P 125 A 120/240 V AC main supply ready assembled
Product Certifications:
UL listed file E-6294
Rohs Exemption Information:
Yes
Load Center Type:
PoN Convertible Mains (breaker)
Line Rated Current:
125 A
Number Of Spaces:
30
Eu Rohs Directive:
Compliant
Circularity Profile:
N/A
Device Composition:
grounding bar (ordered separately)
Awg Gauge:
AWG 6...AWG 2/0 aluminium/copper
Number Of Tandem Circuit Breakers:
30
Depth:
95 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Or Component Type:
Load Center
Country of Origin:
United States
Electrical Connection:
lugs
Number Of Circuits:
60
[Ue] Rated Operational Voltage:
120/240 V AC
Material:
tin plated aluminium: busbar
Range Of Product:
Homeline
Ambient Air Temperature For Operation:
-5°C || 40°C
Enclosure Material:
welded sheet steel
Short-Circuit Current:
22 kA
Cover Type:
combination flush/surface cover
Environmental Disclosure:
ENVPEP1403002
Bus Rated Current:
125.0 A
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Mercury Free:
Yes
Toxic Heavy Metal Free:
Yes
Sustainable Offer Status:
Green Premium product
Surface Finish:
baked enamel Gray
Nema Degree Of Protection:
NEMA 1 indoor enclosure
$812.00

Description

The Homeline load center offer features Homeline circuit breakers, ground fault circuit breakers and arc fault interrupters. Homeline load centers enable the use of a full complement of accessories. Systems are single phase and are rated for indoor use or are rain proof. Homeline load centers are designed for residential and industrial use to protect electrical systems, equipment and people. This Homeline load center has a two pole plug on neutral main supply circuit breaker that is rated at 125A 120/240 VAC single phase. Homeline load center provides a 22 kA breaking capacity. This system provides 30 spaces in a NEMA 1 indoor enclosure with a combination flush/surface indoor cover. The electrical connections are box lugs. The box lugs will accept a wire range of 6 AWG to 2/0 AWG copper or aluminum wire. This Homeline load center has a height of 33.77 inches, a width of 14.25 inches, and depth of 3.74 inches. Homeline load centers are UL Listed.