Schneider Electric

Schneider Electric HRA36060U33X Circuit breaker, PowerPacT H, 60A, 3 pole, 600VAC, 100kA, I-Line, Micrologic 3.2S, 80%, ABC

(No reviews yet) Write a Review
SKU:
HRA36060U33X
MPN:
HRA36060U33X
Condition:
New
Breaking Capacity Code:
R
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Electrical Connection:
I-Line connection, line || lugs, load
Mounting Mode:
I-Line bracket)
Country of Origin:
United States
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Breaking Capacity:
200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Color:
Black
Net Weight:
2.2 kg
Height:
163 mm
Line Rated Current:
60-60 A
Range:
PowerPact
Mercury Free:
Yes
Terminal Identifier:
AL150HD
Communication Interface:
Modbus || Ethernet
Device Application:
distribution
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Circularity Profile:
ENVEOLI2206028EN
Protected Poles Description:
3t
Phase Connection:
ABC
Product Name:
PowerPact H
Pvc Free:
Yes
Ip Degree Of Protection:
front cover IP40 IEC 60529
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Depth:
86 mm
Environmental Disclosure:
ENVPEP2206028EN
Length:
16 mm
Quantity Per Set:
1
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Network Frequency:
50/60 Hz
Weight:
2.2 kg
Mounting Height:
4.5 in
[Ics] Rated Service Breaking Capacity:
150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Trip Unit Name:
MicroLogic 3.2 S
Utilisation Category:
category A
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Continuous Current Rating:
0.8
Ambient Air Temperature For Storage:
-50-85°C
Circuit Breaker Application:
HACR rated
Eu Rohs Directive:
Compliant with Exemptions
Poles Description:
3P
Quality Labels:
CE
$4,393.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Standard with a 3.2S trip unit and an LSI function with a breaking capacity of 100kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 60A, 3 pole, circuit breaker has a breaking capacity of 100kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose