Schneider Electric HRA36100U33X Circuit breaker, PowerPacT H, 100A, 3 pole, 600VAC, 100kA, I-Line, Micrologic 3.2S, 80%, ABC
Schneider Electric
$4,813.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Standard with a 3.2S trip unit and an LSI function with a breaking capacity of 100kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 100A, 3 pole, circuit breaker has a breaking capacity of 100kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Breaking Capacity:
- 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Line Rated Current:
- 100-100 A
- Color:
- Black
- Quality Labels:
- CE
- Rohs Exemption Information:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Range:
- PowerPact
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Continuous Current Rating:
- 0.8
- Protected Poles Description:
- 3t
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Height:
- 4.5 in
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Height:
- 163 mm
- Product Or Component Type:
- circuit breaker
- Height:
- 4.5 in
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Phase Connection:
- ABC
- Environmental Disclosure:
- ENVPEP2206028EN
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Suitability For Isolation:
- yes IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Trip Unit Name:
- MicroLogic 3.2 S
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Operation:
- -25-70°C
- Sustainable Offer Status:
- Green Premium product
- Circularity Profile:
- ENVEOLI2206028EN
- Length:
- 16 mm
- Product Certifications:
- UL || CSA || NOM
- Ambient Air Temperature For Storage:
- -50-85°C
- Breaking Capacity Code:
- R
- Electrical Connection:
- I-Line connection, line || lugs, load
- Mounting Mode:
- I-Line bracket)
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Terminal Identifier:
- AL150HD
- Eu Rohs Directive:
- Compliant with Exemptions
- Country of Origin:
- United States
- Depth:
- 86 mm
- Utilisation Category:
- category A
- Product Name:
- PowerPact H
- Poles Description:
- 3P
- [Ics] Rated Service Breaking Capacity:
- 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- Wire Stripping Length:
- 16 mm
- Control Type:
- toggle