- Wire Stripping Length:
- 16 mm
- Pvc Free:
- Yes
- Breaking Capacity:
- 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
- Communication Interface:
- Modbus || Ethernet
- [Ith] Conventional Free Air Thermal Current:
- 1.5-25 A
- Quality Labels:
- CE
- Terminal Identifier:
- AL150HD
- Network Frequency:
- 50/60 Hz
- Suitability For Isolation:
- yes IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70°C
- Magnetic Tripping Current:
- 9-325 A
- Device Application:
- distribution
- Trip Unit Technology:
- thermal-magnetic
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection:
- lugs, line || lugs, load
- Product Certifications:
- UL || CSA || NOM
- Net Weight:
- 2.2 kg
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Country of Origin:
- United States
- Weight:
- 2.2 kg
- Rohs Exemption Information:
- Yes
- Circularity Profile:
- ENVEOLI2206028EN
- Quantity Per Set:
- 1
- Environmental Disclosure:
- ENVPEP2206028EN
- Product Or Component Type:
- Motor Circuit Protector
- [Ics] Rated Service Breaking Capacity:
- 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Product Name:
- PowerPact H
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Breaking Capacity Code:
- R
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Protected Poles Description:
- 3t
- Line Rated Current:
- 30-30 A
- Continuous Current Rating:
- 0.8
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 86 mm
- Mercury Free:
- Yes
- Color:
- Black
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Mode:
- unit mount lug)