- Electrical Connection:
- lugs, line || lugs, load
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Net Weight:
- 2.2 kg
- Circuit Breaker Application:
- HACR rated
- Circularity Profile:
- ENVEOLI2206028EN
- Product Name:
- PowerPact H
- Utilisation Category:
- category A
- Weight:
- 2.2 kg
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Line Rated Current:
- 150-150 A
- Trip Unit Name:
- MicroLogic 3.2
- Control Type:
- toggle
- Depth:
- 86 mm
- Pvc Free:
- Yes
- Ambient Air Temperature For Storage:
- -50-85°C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Device Application:
- distribution
- Color:
- Black
- Breaking Capacity:
- 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Sustainable Offer Status:
- Green Premium product
- Continuous Current Rating:
- 0.8
- Terminal Identifier:
- AL150HD
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Eu Rohs Directive:
- Compliant with Exemptions
- Quality Labels:
- CE
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Suitability For Isolation:
- yes IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Protected Poles Description:
- 3t
- Mercury Free:
- Yes
- Range:
- PowerPact
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Mode:
- unit mount lug)
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mounting Support:
- lug
- Communication Interface:
- Modbus || Ethernet
- Ambient Air Temperature For Operation:
- -25-70°C
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Length:
- 16 mm