Schneider Electric JDL34250WU43X Circuit breaker, PowerPacT J, 250A, 3 pole, 480VAC, 18kA, lugs, Micrologic 5.2A, 80%, mission critical

(No reviews yet) Write a Review
SKU:
JDL34250WU43X
MPN:
JDL34250WU43X
Condition:
New
Ambient Air Temperature For Operation:
-25-70°C
Width:
104 mm
Pollution Degree:
3 IEC 60947-1
Device Application:
distribution
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Environmental Disclosure:
ENVPEP2206032EN
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Electrical Connection:
lugs, line || lugs, load
Breaking Capacity Code:
D
Rohs Exemption Information:
Yes
Terminal Identifier:
AL250JD
[Ue] Rated Operational Voltage:
480/277 V AC 50/60 Hz IEC 60947-3
Communication Interface:
Modbus || Ethernet
Sustainable Offer Status:
Green Premium product
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Product Or Component Type:
circuit breaker
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Mercury Free:
Yes
Range:
PowerPact
Trip Unit Technology:
electronic, ammeter, MicroLogic 5.2 A, LSI
Country of Origin:
United States
Poles Description:
3P
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Protection Type:
overload protection || short-circuit protection
Length:
25 mm
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Line Rated Current:
250-250 A
Depth:
86 mm
Eu Rohs Directive:
Compliant with Exemptions
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Quality Labels:
CE
Weight:
2.4 kg
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Product Name:
PowerPact J
Warranty:
18 months
Mounting Mode:
unit mount lug)
Product Certifications:
UL || CSA || NOM
Circuit Breaker Application:
HACR rated
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Control Type:
toggle
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Continuous Current Rating:
0.8
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ambient Air Temperature For Storage:
-50-85°C
Wire Stripping Length:
25 mm
$4,809.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Ammeter with a 5.2A trip unit and an LSI function with a breaking capacity of 18kA at 480VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 18kA at 480VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose