- Rohs Exemption Information:
- Yes
- Breaking Capacity Code:
- G
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- PowerPact J
- Mounting Support:
- lug
- Ip Degree Of Protection:
- front cover IP40
- Weight:
- 2.4 kg
- Circuit Breaker Application:
- HACR rated
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Magnetic Tripping Current:
- 2250-2250 A
- Warranty:
- 18 months
- Pvc Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Suitability For Isolation:
- yes IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Range:
- PowerPact
- Environmental Disclosure:
- ENVPEP2206031EN
- Protection Type:
- overload protection || short-circuit protection
- Height:
- 191 mm
- Electrical Connection:
- lugs, line || terminal nut, load
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Height:
- 4.5 in
- Utilisation Category:
- category A
- Country of Origin:
- United States
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Storage:
- -50-85°C
- Trip Unit Technology:
- thermal-magnetic
- Pollution Degree:
- 3 IEC 60947-1
- Continuous Current Rating:
- 0.8
- Circularity Profile:
- ENVEOLI2206031EN
- Poles Description:
- 3P
- Network Frequency:
- 50/60 Hz
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Device Application:
- distribution
- Line Rated Current:
- 225-225 A
- Communication Interface:
- Modbus || Ethernet
- Depth:
- 86 mm
- Control Type:
- toggle
- Mounting Height:
- 4.5 in
- Wire Stripping Length:
- 25 mm
- Phase Connection:
- ABC
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Operation:
- -25-70°C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.