- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Country of Origin:
- United States
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Poles Description:
- 3P
- Ip Degree Of Protection:
- front cover IP40
- Network Frequency:
- 50/60 Hz
- Depth:
- 86 mm
- Wire Stripping Length:
- 25 mm
- Height:
- 191 mm
- Mounting Support:
- base
- Product Certifications:
- UL || CSA || NOM
- Circuit Breaker Application:
- HACR rated
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- ENVEOLI2206031EN
- Phase Connection:
- BA
- Weight:
- 2.4 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Quality Labels:
- CE
- Length:
- 25 mm
- Mounting Mode:
- plug-in base)
- Warranty:
- 18 months
- Pvc Free:
- Yes
- Electrical Connection:
- plug-in, line || plug-in, load
- Device Application:
- distribution
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Height:
- 4.5 in
- Trip Unit Technology:
- thermal-magnetic
- Magnetic Tripping Current:
- 2250-2250 A
- Mercury Free:
- Yes
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Pollution Degree:
- 3 IEC 60947-1
- Range:
- PowerPact
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Product Name:
- PowerPact J
- Environmental Disclosure:
- ENVPEP2206031EN
- Rohs Exemption Information:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Communication Interface:
- Modbus || Ethernet
- Mounting Height:
- 4.5 in
- Protection Type:
- overload protection || short-circuit protection
- Line Rated Current:
- 225-225 A
- Utilisation Category:
- category A
- Suitability For Isolation:
- yes IEC 60947-2
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals