Schneider Electric

Schneider Electric JLL36250CU43X Circuit breaker, PowerPacT J, 250A, 3 pole, 600VAC, 50kA, lugs, Micrologic 5.2A, 100%

(No reviews yet) Write a Review
SKU:
JLL36250CU43X
MPN:
JLL36250CU43X
Condition:
New
Mercury Free:
Yes
Breaking Capacity:
125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
Mounting Support:
lug
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Warranty:
18 months
Height:
191 mm
Trip Unit Name:
MicroLogic 5.2 A
Country of Origin:
United States
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
front cover IP40
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
86 mm
Pvc Free:
Yes
Circularity Profile:
ENVEOLI2206032EN
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Product Or Component Type:
circuit breaker
Ambient Air Temperature For Storage:
-50-85°C
Circuit Breaker Application:
HACR rated
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Network Frequency:
50/60 Hz
Terminal Identifier:
AL250JD
Width:
104 mm
Wire Stripping Length:
25 mm
Product Certifications:
UL || CSA || NOM
Communication Interface:
Modbus
Eu Rohs Directive:
Compliant with Exemptions
Net Weight:
2.4 kg
Length:
25 mm
Trip Unit Technology:
electronic, ammeter, MicroLogic 5.2 A, LSI
Utilisation Category:
category A
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Electrical Connection:
lugs, line || lugs, load
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Line Rated Current:
250-250 A
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Environmental Disclosure:
ENVPEP2206032EN
Quality Labels:
CE
Protection Type:
overload protection || short-circuit protection
Weight:
2.4 kg
Control Type:
toggle
Sustainable Offer Status:
Green Premium product
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Continuous Current Rating:
1
Ambient Air Temperature For Operation:
-25-70°C
[Ics] Rated Service Breaking Capacity:
125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Pollution Degree:
3
Rohs Exemption Information:
Yes
$9,653.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Ammeter with a 5.2A trip unit and an LSI function with a breaking capacity of 50kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose