- Ambient Air Temperature For Operation:
- -25-70°C
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Eu Rohs Directive:
- Compliant with Exemptions
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Quality Labels:
- CE
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Storage:
- -50-85°C
- Line Rated Current:
- 250-250 A
- Depth:
- 86 mm
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Warranty:
- 18 months
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Product Or Component Type:
- circuit breaker
- Protection Type:
- overload protection || short-circuit protection
- Mounting Support:
- lug
- Net Weight:
- 2.4 kg
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Continuous Current Rating:
- 0.8
- Length:
- 25 mm
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Terminal Identifier:
- AL250JD
- Sustainable Offer Status:
- Green Premium product
- Control Type:
- toggle
- Weight:
- 2.4 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Poles Description:
- 3P
- Electrical Connection:
- lugs, line || lugs, load
- Network Frequency:
- 50/60 Hz
- Utilisation Category:
- category A
- Product Certifications:
- UL || CSA || NOM
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Ip Degree Of Protection:
- front cover IP40
- Trip Unit Name:
- MicroLogic 3.2 S
- Circularity Profile:
- ENVEOLI2206032EN
- Wire Stripping Length:
- 25 mm
- Pvc Free:
- Yes
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Pollution Degree:
- 3
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mercury Free:
- Yes
- Communication Interface:
- Modbus