Schneider Electric

Schneider Electric JLM36250 Circuit breaker, PowerPacT J, 250A, 3 pole, 600VAC, 50kA, lugs, thermal magnetic, 80%

(No reviews yet) Write a Review
SKU:
JLM36250
MPN:
JLM36250
Condition:
New
Pvc Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Or Component Type:
circuit breaker
Electrical Connection:
lugs, line || terminal nut, load
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile:
ENVEOLI2206031EN
Rohs Exemption Information:
Yes
Net Weight:
2.4 kg
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Breaking Capacity:
125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
Magnetic Hold Current:
1250 A
Depth:
86 mm
Ambient Air Temperature For Storage:
-50-85°C
Mounting Support:
lug
Local Signaling:
switched off (OFF) 1 trip indicator green)
Protection Type:
overload protection || short-circuit protection
Sustainable Offer Status:
Green Premium product
Terminal Identifier:
AL250JD
Product Certifications:
UL || CSA || NOM
Network Frequency:
50/60 Hz
Quality Labels:
CE
Ambient Air Temperature For Operation:
-25-70°C
Suitability For Isolation:
yes IEC 60947-2
Weight:
2.4 kg
Continuous Current Rating:
0.8
Magnetic Tripping Current:
2500-2500 A
Wire Stripping Length:
25 mm
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Communication Interface:
Modbus
Control Type:
toggle
Trip Unit Technology:
thermal-magnetic
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Poles Description:
3P
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Utilisation Category:
category A
Environmental Disclosure:
ENVPEP2206031EN
Ip Degree Of Protection:
front cover IP40
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Mounting Mode:
unit mount lug)
Eu Rohs Directive:
Compliant with Exemptions
Country of Origin:
United States
$8,993.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 50kA at 600VAC. Per the National Electric Code® (NEC®) and the Canadian Electrical Code, standard circuit breakers may only be applied continuously at up to 80% of their rating. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on the line side and terminal nuts on the load side. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.