Schneider Electric

Schneider Electric LADN403 Auxiliary contact block, TeSys Deca, 4NO, front mounting, spring terminals

(No reviews yet) Write a Review
SKU:
LADN403
MPN:
LADN403
Condition:
New
Color:
dark grey
Country of Origin:
France
Range:
TeSys || TeSys Deca
Pole Contact Composition:
4 NO
Ambient Air Temperature For Operation:
-5-60°C
Rohs Exemption Information:
Yes
Ambient Air Temperature For Storage:
-60-80°C
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Irms Rated Making Capacity:
140 A AC conforming to IEC 60947-5-1 || 250 A DC conforming to IEC 60947-5-1
[Ue] Rated Operational Voltage:
690 V AC 25...400 Hz
[Ie] Rated Operational Current:
6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
Operating Altitude:
9842.52 ft (3000 m)
Product Name:
TeSys Deca
Auxiliary Contacts Operation:
instantaneous
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || EN 50012 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
Reach Free Of Svhc:
Yes
Depth:
42 mm
Sustainable Offer Status:
Green Premium product
Insulation Resistance:
> 10 MOhm
Mechanical Durability:
30 Mcycles
Net Weight:
0.05 kg
Eu Rohs Directive:
Compliant
Product Certifications:
CB Scheme || UL || CSA || CCC || EAC || UKCA
Warranty:
18 months
Connections - Terminals:
spring terminals 2 2.5-2.5 mm²flexible without cable end || spring terminals 2 2.5-2.5 mm²rigid
Toxic Heavy Metal Free:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Environmental Disclosure:
ENVPEP110807EN_V3
Mercury Free:
Yes
Mounting Location:
front
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Product Or Component Type:
auxiliary contact block
Circularity Profile:
N/A
Environmental Characteristic:
normal environment
Protection Type:
gG fuse 10 A
Minimum Switching Voltage:
17 V
Sustainable Packaging:
Yes
Protective Treatment:
TH IEC 60068
Minimum Switching Current:
5 mA
[Ui] Rated Insulation Voltage:
690 V IEC 60947-5-1 || 600 V UL || 600 V CSA
Range Compatibility:
TeSys D CAD || TeSys D LC1D || TeSys Deca CAD || TeSys Deca LC1D
Weight:
0.05 kg
Permissible Short-Time Rating:
100 A 60°C 1 s || 120 A 60°C 500 ms || 140 A 60°C 100 ms
Ip Degree Of Protection:
IP2X conforming to IEC 60529
Non-Overlap Time:
1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
Device Short Name:
LADN
$54.60

Description

TeSys Deca instantaneous auxiliary contact block, for contactors LC1D and control relays CAD. It provides 4NO contacts rated up to 10A/690V AC, connection by spring terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).