- Operating Altitude:
- 9842.52 ft (3000 m)
- Product Name:
- TeSys Deca
- Rohs Exemption Information:
- Yes
- Connections - Terminals:
- lugs-ring terminals 8 mm)
- Irms Rated Making Capacity:
- 140 A AC conforming to IEC 60947-5-1 || 250 A DC conforming to IEC 60947-5-1
- Ip Degree Of Protection:
- IP2X conforming to IEC 60529
- Product Certifications:
- CB Scheme || UL || CSA || CCC || EAC || UKCA
- Non-Overlap Time:
- 1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
- Minimum Switching Voltage:
- 17 V
- Country of Origin:
- France
- [Ie] Rated Operational Current:
- 6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
- Depth:
- 42 mm
- Weight:
- 0.05 kg
- Range:
- TeSys || TeSys Deca
- Net Weight:
- 0.05 kg
- Sustainable Packaging:
- Yes
- Standards:
- EN/IEC 60947-5-1 || GB/T 14048.5 || EN 50012 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
- Tightening Torque:
- 1.7 N.m flat Ø 6 mm M3.5 || 1.7 N.m Philips No 2 M3.5 || 1.7 N.m pozidriv No 2 M3.5
- Reach Free Of Svhc:
- Yes
- Environmental Disclosure:
- ENVPEP110807EN_V3
- Mechanical Durability:
- 30 Mcycles
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Auxiliary Contacts Operation:
- instantaneous
- Circularity Profile:
- N/A
- Protection Type:
- gG fuse 10 A
- Ambient Air Temperature For Operation:
- -5-60°C
- Environmental Characteristic:
- normal environment
- Minimum Switching Current:
- 5 mA
- [Ui] Rated Insulation Voltage:
- 690 V IEC 60947-5-1 || 600 V UL || 600 V CSA
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Warranty:
- 18 months
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C)
- Permissible Short-Time Rating:
- 100 A 60°C 1 s || 120 A 60°C 500 ms || 140 A 60°C 100 ms
- Protective Treatment:
- TH IEC 60068
- Eu Rohs Directive:
- Compliant
- Ambient Air Temperature For Storage:
- -60-80°C
- Device Short Name:
- LADN
- Insulation Resistance:
- > 10 MOhm
- Pole Contact Composition:
- 4 NO
- Sustainable Offer Status:
- Green Premium product
- Mercury Free:
- Yes
- Range Compatibility:
- TeSys D CAD || TeSys D LC1D || TeSys F LC1F || TeSys F CR1F || TeSys Deca CAD || TeSys Deca LC1D
- Mounting Location:
- front
- [Ue] Rated Operational Voltage:
- 690 V AC 25...400 Hz
- Color:
- dark grey
- Toxic Heavy Metal Free:
- Yes