Schneider Electric

Schneider Electric LC1D093G7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D093G7
MPN:
LC1D093G7
Condition:
New
Net Weight:
0.32 kg
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Eu Rohs Directive:
Compliant
Device Short Name:
LC1D
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Rohs Exemption Information:
Yes
Mounting Support:
rail || plate
Power Dissipation Per Pole:
1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
Pole Contact Composition:
3 NO
Pollution Degree:
3
Warranty:
18 months
Protective Treatment:
THIEC 60068-2-30
Pvc Free:
Yes
Maximum Horse Power Rating:
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phas
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Contactor Application:
motor control || resistive load
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Product Or Component Type:
contactor
Control Circuit Type:
AC 50/60 Hz
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Toxic Heavy Metal Free:
Yes
Country of Origin:
United States
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Overvoltage Category:
III
Coil Technology:
without built-in suppressor module
Signaling Circuit Frequency:
25...400 Hz
Mechanical Durability:
15 Mcycles
Operating Altitude:
0...9842.52 ft (0...3000 m)
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Minimum Switching Current:
5 mA for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Environmental Disclosure:
ENVPEP1501004
Connections - Terminals:
power circuit: spring terminals 1 2.5-2.5 mm² - cable stiffness: flexible without cable end || power circuit: spring terminals 2 2.5-2.5 mm² - cable stiffness: flexible without cable end || control circuit: spring terminals 1 2.5-2.5 mm² - cable s
Sustainable Offer Status:
Green Premium product
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Mercury Free:
Yes
Electrical Durability:
0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V || 2 Mcycles 9 A AC-3e <= 440 V
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Poles Description:
3P
Width:
45 mm
Insulation Resistance:
> 10 MOhm for Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Average Impedance:
2.5 mOhm - Ith 16 A 50 Hz for power circuit
Weight:
0.32 kg
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 16 A (at 60°C) for power circuit
$112.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.