Schneider Electric

Schneider Electric LC1D093P7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, 230VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D093P7
MPN:
LC1D093P7
Condition:
New
Minimum Switching Voltage:
17 V for Signaling circuit
Operating Time:
12...22 ms closing || 4...19 ms opening
Insulation Resistance:
> 10 MOhm for Signaling circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 16 A (at 60°C) for power circuit
Mercury Free:
Yes
Poles Description:
3P
Width:
45 mm
Eu Rohs Directive:
Compliant
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 20 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Signaling Circuit Frequency:
25...400 Hz
Average Impedance:
2.5 mOhm - Ith 16 A 50 Hz for power circuit
Motor Power Kw:
2.2 kW at 220...230 V AC 50/60 Hz (AC-3) || 4 kW at 380...400 V AC 50/60 Hz (AC-3) || 4 kW at 415 V AC 50/60 Hz (AC-3) || 4 kW at 440 V AC 50/60 Hz (AC-3) || 5.5 kW at 500 V AC 50/60 Hz (AC-3) || 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 2.2 kW at
Connections - Terminals:
power circuit: spring terminals 1 2.5-2.5 mm² - cable stiffness: flexible without cable end || power circuit: spring terminals 2 2.5-2.5 mm² - cable stiffness: flexible without cable end || control circuit: spring terminals 1 2.5-2.5 mm² - cable s
Overvoltage Category:
III
Protective Cover:
with
Power Dissipation Per Pole:
1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Range Of Product:
TeSys Deca
Warranty:
18 months
Compatibility Code:
LC1D
Mechanical Durability:
15 Mcycles
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Control Circuit Type:
AC 50/60 Hz
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Pvc Free:
Yes
Auxiliary Contact Composition:
1 NO + 1 NC
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Toxic Heavy Metal Free:
Yes
Heat Dissipation:
2-3 W at 50/60 Hz
Depth:
86 mm
Product Or Component Type:
contactor
Rohs Exemption Information:
Yes
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Pollution Degree:
3
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Environmental Disclosure:
ENVPEP1501004
Weight:
0.32 kg
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
$112.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.