Schneider Electric

Schneider Electric LC1D096BD IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D096BD
MPN:
LC1D096BD
Condition:
New
Electrical Durability:
0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V || 2 Mcycles 9 A AC-3e <= 440 V
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Sustainable Offer Status:
Green Premium product
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Flame Retardance:
V1 conforming to UL 94
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Rohs Exemption Information:
Yes
Control Circuit Type:
DC standard
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Contactor Application:
motor control || resistive load
Poles Description:
3P
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Eu Rohs Directive:
Compliant with Exemptions
Overvoltage Category:
III
Minimum Switching Voltage:
17 V for Signaling circuit
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Circularity Profile:
ENVEOLI1102030EN
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Insulation Resistance:
> 10 MOhm for Signaling circuit
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Warranty:
18 months
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Operating Altitude:
0...9842.52 ft (0...3000 m)
Compatibility Code:
LC1D
Pvc Free:
Yes
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 8 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Signaling Circuit Frequency:
25...400 Hz
Mercury Free:
Yes
Minimum Switching Current:
5 mA for Signaling circuit
Range Of Product:
TeSys Deca
Maximum Operating Rate:
3600 cyc/h 60°C
Mounting Support:
plate || rail
Weight:
0.48 kg
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Fire Resistance:
850°C IEC 60695-2-1
Auxiliary Contact Composition:
1 NO + 1 NC
Protective Treatment:
THIEC 60068-2-30
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight:
0.48 kg
$119.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as stanard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose