Schneider Electric

Schneider Electric LC1D096SD IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, 72VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D096SD
MPN:
LC1D096SD
Condition:
New
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Insulation Resistance:
> 10 MOhm for Signaling circuit
Pole Contact Composition:
3 NO
Mercury Free:
Yes
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Inrush Power In W:
5.4-5.4 W 20°C)
Compatibility Code:
LC1D
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Poles Description:
3P
Warranty:
18 months
Eu Rohs Directive:
Compliant with Exemptions
Motor Power Kw:
2.2 kW at 220...230 V AC 50/60 Hz (AC-3) || 4 kW at 380...400 V AC 50/60 Hz (AC-3) || 4 kW at 415 V AC 50/60 Hz (AC-3) || 4 kW at 440 V AC 50/60 Hz (AC-3) || 5.5 kW at 500 V AC 50/60 Hz (AC-3) || 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 2.2 kW at
Overvoltage Category:
III
Protective Treatment:
THIEC 60068-2-30
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 8 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Device Short Name:
LC1D
Minimum Switching Current:
5 mA for Signaling circuit
Width:
45 mm
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Mounting Support:
plate || rail
Product Or Component Type:
contactor
Weight:
0.48 kg
Circularity Profile:
ENVEOLI1102030EN
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Mechanical Durability:
30 Mcycles
Environmental Disclosure:
ENVPEP110230EN
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Pvc Free:
Yes
Sustainable Offer Status:
Green Premium product
Minimum Switching Voltage:
17 V for Signaling circuit
Signaling Circuit Frequency:
25...400 Hz
Depth:
95 mm
Rohs Exemption Information:
Yes
Auxiliary Contact Composition:
1 NO + 1 NC
Fire Resistance:
850°C IEC 60695-2-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Range Of Product:
TeSys Deca
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Maximum Operating Rate:
3600 cyc/h 60°C
Contactor Application:
resistive load || motor control
Utilisation Category:
AC-4 || AC-3 || AC-1 || AC-3e
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
$119.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a low consumption 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as stanard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose