Schneider Electric

Schneider Electric LC1D096SLS207 IEC contactor, TeSys D, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 72VDC, open style

(No reviews yet) Write a Review
SKU:
LC1D096SLS207
MPN:
LC1D096SLS207
Condition:
New
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
Country of Origin:
France
Warranty:
18 months
Hold-In Power Consumption In W:
4-4 W 20°C
Mercury Free:
Yes
Device Short Name:
LC1D
Net Weight:
0.32 kg
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Operating Altitude:
0...9842.52 ft (0...3000 m)
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 9.5 mm
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Sustainable Offer Status:
Green Premium product
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Pole Contact Composition:
3 NO
Pvc Free:
Yes
Inrush Power In W:
4-4 W 20°C)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Weight:
0.32 kg
Rohs Exemption Information:
Yes
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Mechanical Durability:
30 Mcycles
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Overvoltage Category:
III
Width:
45 mm
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Height:
77 mm
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Fire Resistance:
850°C IEC 60695-2-1
Time Constant:
37 ms
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-70°C operational DC
Protective Cover:
with
Control Circuit Type:
DC low consumption
Product Certifications:
IEC || CCC || EAC || UA || TR || UKCA
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Minimum Switching Current:
5 mA for Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Coil Technology:
with integral suppression device
Contactor Application:
resistive load || motor control
Mounting Support:
rail || plate
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3
Operating Time:
77±15 % ms closing || 25±20 % ms opening
Compatibility Code:
LC1D
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Eu Rohs Directive:
Compliant with Exemptions
Maximum Operating Rate:
3600 cyc/h 60°C
Motor Power Kw:
2.2 kW at 220/230 V AC 50 Hz (AC-3) || 4 kW at 380/400 V AC 50 Hz (AC-3) || 4 kW at 415 V AC 50 Hz (AC-3) || 4 kW at 440 V AC 50 Hz (AC-3) || 5.5 kW at 500 V AC 50 Hz (AC-3) || 5.5 kW at 660/690 V AC 50 Hz (AC-3) || 2.2 kW at 220/230 V AC 50 Hz (AC-3
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Range:
TeSys || TeSys Deca
$150.00

Description

This TeSys D contactor has been designed for motor control in railway applications. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a low consumption 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as stanard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose