Schneider Electric

Schneider Electric LC1D098B7 IEC contactor, TeSys Deca, nonreversing, 20A resistive, 4 pole, 2 NO and 2 NC, 24VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D098B7
MPN:
LC1D098B7
Condition:
New
Electrical Durability:
0.3 Mcycles 20 A AC-1 <= 690 V
Minimum Switching Current:
5 mA for Signaling circuit
Device Short Name:
LC1D
Fire Resistance:
850°C IEC 60695-2-1
Contactor Application:
resistive load
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Mechanical Durability:
15 Mcycles
Rohs Exemption Information:
Yes
Height:
85 mm
Flame Retardance:
V1 conforming to UL 94
Operating Time:
12...22 ms closing || 4...19 ms opening
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Product Or Component Type:
contactor
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Environmental Disclosure:
ENVPEP1501004
Circularity Profile:
ENVEOLI1501004
Compatibility Code:
LC1D
Minimum Switching Voltage:
17 V for Signaling circuit
Coil Technology:
without built-in suppressor module
Toxic Heavy Metal Free:
Yes
Poles Description:
4P
Country of Origin:
France
Sustainable Offer Status:
Green Premium product
Eu Rohs Directive:
Compliant
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Operating Altitude:
0...9842.52 ft (0...3000 m)
Range Of Product:
TeSys Deca
Pole Contact Composition:
2 NO + 2 NC
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Net Weight:
0.365 kg
Ip Degree Of Protection:
IP20 front face IEC 60529
Mounting Support:
plate || rail
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Protective Cover:
with
Pvc Free:
Yes
Control Circuit Type:
AC 50/60 Hz
Weight:
0.365 kg
Standards:
CSA C22.2 No 60947-4-1 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Power Dissipation Per Pole:
1.56 W AC-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Maximum Operating Rate:
3600 cyc/h 60°C
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Width:
45 mm
Product Certifications:
UL || CCC || CSA || UKCA || EAC || CB || EU-RO-MR by DNV-GL
$130.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.