Schneider Electric

Schneider Electric LC1D098ED IEC contactor, TeSys Deca, nonreversing, 20A resistive, 4 pole, 2 NO and 2 NC, 48VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D098ED
MPN:
LC1D098ED
Condition:
New
Eu Rohs Directive:
Compliant with Exemptions
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Fire Resistance:
850°C IEC 60695-2-1
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-60°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Contactor Application:
resistive load
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Uc] Control Circuit Voltage:
48 V DC
Device Short Name:
LC1D
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Flame Retardance:
V1 conforming to UL 94
Pvc Free:
Yes
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Maximum Operating Rate:
3600 cyc/h 60°C
Minimum Switching Voltage:
17 V for Signaling circuit
Range Of Product:
TeSys Deca
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Weight:
0.525 kg
Control Circuit Type:
DC standard
Product Certifications:
UL || CCC || CSA || UKCA || EAC || CB || EU-RO-MR by DNV-GL
Protective Cover:
with
Operating Altitude:
0...9842.52 ft (0...3000 m)
Standards:
CSA C22.2 No 60947-4-1 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Time Constant:
28 ms
Insulation Resistance:
> 10 MOhm for Signaling circuit
Power Dissipation Per Pole:
1.56 W AC-1
Warranty:
18 months
Electrical Durability:
0.3 Mcycles 20 A AC-1 <= 690 V
Circularity Profile:
ENVEOLI1102030EN
Country of Origin:
France
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Product Or Component Type:
contactor
Mounting Support:
rail || plate
Pole Contact Composition:
2 NO + 2 NC
Protective Treatment:
THIEC 60068-2-30
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Net Weight:
0.525 kg
Operating Time:
63±15 % ms closing || 20±20 % ms opening
$138.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 1.16 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose