Schneider Electric

Schneider Electric LC1D098P7 IEC contactor, TeSys Deca, nonreversing, 20A resistive, 4 pole, 2 NO and 2 NC, 230VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D098P7
MPN:
LC1D098P7
Condition:
New
Minimum Switching Voltage:
17 V for Signaling circuit
Coil Technology:
without built-in suppressor module
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Mechanical Durability:
15 Mcycles
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Compatibility Code:
LC1D
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Power Dissipation Per Pole:
1.56 W AC-1
Fire Resistance:
850°C IEC 60695-2-1
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Protective Treatment:
THIEC 60068-2-30
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Pvc Free:
Yes
Mounting Support:
plate || rail
Control Circuit Type:
AC 50/60 Hz
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz
Country of Origin:
Indonesia
Net Weight:
0.365 kg
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Protective Cover:
with
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Standards:
CSA C22.2 No 60947-4-1 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Flame Retardance:
V1 conforming to UL 94
Signaling Circuit Frequency:
25...400 Hz
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Pollution Degree:
3
Height:
85 mm
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Warranty:
18 months
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Poles Description:
4P
Mercury Free:
Yes
Toxic Heavy Metal Free:
Yes
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Range Of Product:
TeSys Deca
Weight:
0.365 kg
Environmental Disclosure:
ENVPEP1501004
Product Or Component Type:
contactor
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Auxiliary Contact Composition:
1 NO + 1 NC
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Circularity Profile:
ENVEOLI1501004
$130.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose