Schneider Electric

Schneider Electric LC1D09F7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D09F7
MPN:
LC1D09F7
Condition:
New
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
Power Dissipation Per Pole:
1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Minimum Switching Current:
5 mA for Signaling circuit
Fire Resistance:
850°C IEC 60695-2-1
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Minimum Switching Voltage:
17 V for Signaling circuit
Environmental Disclosure:
ENVPEP1501004
Eu Rohs Directive:
Compliant
Device Short Name:
LC1D
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Toxic Heavy Metal Free:
Yes
Depth:
86 mm
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
0.32 kg
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Height:
77 mm
Operating Altitude:
0...9842.52 ft (0...3000 m)
Operating Time:
12...22 ms closing || 4...19 ms opening
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Width:
45 mm
Utilisation Category:
AC-1 || AC-3 || AC-4 || AC-3e
Signaling Circuit Frequency:
25...400 Hz
Ip Degree Of Protection:
IP20 front face IEC 60529
Maximum Operating Rate:
3600 cyc/h 60°C
Country of Origin:
Singapore
Circularity Profile:
ENVEOLI1501004
Rohs Exemption Information:
Yes
Maximum Horse Power Rating:
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phas
Pollution Degree:
3
Motor Power Kw:
2.2 kW at 220...230 V AC 50/60 Hz (AC-3) || 4 kW at 380...400 V AC 50/60 Hz (AC-3) || 4 kW at 415...440 V AC 50/60 Hz (AC-3) || 5.5 kW at 500 V AC 50/60 Hz (AC-3) || 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 2.2 kW at 400 V AC 50/60 Hz (AC-4) || 2.
Overvoltage Category:
III
Product Or Component Type:
contactor
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Sustainable Offer Status:
Green Premium product
Control Circuit Type:
AC 50/60 Hz standard
Range Of Product:
TeSys Deca
Auxiliary Contact Composition:
1 NO + 1 NC
Coil Technology:
without built-in suppressor module
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
$112.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.