Schneider Electric

Schneider Electric LC1D09JD IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D09JD
MPN:
LC1D09JD
Condition:
New
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Warranty:
18 months
Protective Cover:
with
Fire Resistance:
850°C IEC 60695-2-1
Flame Retardance:
V1 conforming to UL 94
Signaling Circuit Frequency:
25...400 Hz
Overvoltage Category:
III
[Uc] Control Circuit Voltage:
12 V DC
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Electrical Durability:
0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V || 2 Mcycles 9 A AC-3e <= 440 V
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Short Name:
LC1D
Insulation Resistance:
> 10 MOhm for Signaling circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Maximum Horse Power Rating:
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phas
Mounting Support:
rail || plate
Net Weight:
0.48 kg
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Sustainable Offer Status:
Green Premium product
Auxiliary Contact Composition:
1 NO + 1 NC
Contactor Application:
resistive load || motor control
Width:
45 mm
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Ip Degree Of Protection:
IP20 front face IEC 60529
Minimum Switching Current:
5 mA for Signaling circuit
Mercury Free:
Yes
Eu Rohs Directive:
Compliant with Exemptions
Time Constant:
28 ms
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Compatibility Code:
LC1D
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Pvc Free:
Yes
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Control Circuit Type:
DC standard
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Environmental Disclosure:
ENVPEP110230EN
Inrush Power In W:
5.4-5.4 W 20°C)
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Country of Origin:
Singapore
Operating Altitude:
0...9842.52 ft (0...3000 m)
$119.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose