Schneider Electric LC1D09N7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 415VAC 50/60Hz coil, open style
Schneider Electric
$112.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 415 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Utilisation Category:
- AC-3 || AC-1 || AC-4 || AC-3e
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Mercury Free:
- Yes
- Heat Dissipation:
- 2-3 W at 50/60 Hz
- Sustainable Offer Status:
- Green Premium product
- Coil Technology:
- without built-in suppressor module
- Mechanical Durability:
- 15 Mcycles
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Power Dissipation Per Pole:
- 1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Height:
- 77 mm
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Mounting Support:
- rail || plate
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Contactor Application:
- motor control || resistive load
- Toxic Heavy Metal Free:
- Yes
- Pole Contact Composition:
- 3 NO
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Control Circuit Type:
- AC 50/60 Hz
- [Uc] Control Circuit Voltage:
- 415 V AC 50/60 Hz
- Minimum Switching Current:
- 5 mA for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
- [Icw] Rated Short-Time Withstand Current:
- 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Rohs Exemption Information:
- Yes
- Connections - Terminals:
- power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Width:
- 45 mm
- Eu Rohs Directive:
- Compliant
- Maximum Horse Power Rating:
- 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phas
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Country of Origin:
- France
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Net Weight:
- 0.32 kg
- Environmental Disclosure:
- ENVPEP1501004
- Flame Retardance:
- V1 conforming to UL 94
- Warranty:
- 18 months
- Product Or Component Type:
- contactor
- Device Short Name:
- LC1D
- Range Of Product:
- TeSys Deca
- Protective Cover:
- with
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Electrical Durability:
- 0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V || 2 Mcycles 9 A AC-3e <= 440 V
- Protective Treatment:
- THIEC 60068-2-30
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1