Schneider Electric

Schneider Electric LC1D115004G6 IEC contactor, TeSys Deca, nonreversing, 200A resistive, 4 pole, 4 NO, 120VAC 60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D115004G6
MPN:
LC1D115004G6
Condition:
New
Depth:
132 mm
Eu Rohs Directive:
Compliant with Exemptions
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit
Sustainable Offer Status:
Green Premium product
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Range Of Product:
TeSys Deca
Mounting Support:
rail || plate
Poles Description:
4P
Power Dissipation Per Pole:
24 W AC-1
Rohs Exemption Information:
Yes
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² -
Pvc Free:
Yes
Overvoltage Category:
III
Contactor Application:
resistive load
Environmental Disclosure:
ENVPEP060301EN
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Fire Resistance:
850°C IEC 60695-2-1
[Uc] Control Circuit Voltage:
120 V AC 60 Hz
Mechanical Durability:
8 Mcycles
Country of Origin:
Czechia
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Operating Time:
6...20 ms opening || 20...50 ms closing
Product Certifications:
GOST || RINA || UL || BV || GL || CCC || LROS (Lloyds register of shipping) || CSA || DNV || UKCA
Control Circuit Type:
AC 60 Hz
Coil Technology:
without built-in suppressor module
Circularity Profile:
ENVEOLI100405EN
Pole Contact Composition:
4 NO
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
Height:
158 mm
Range:
TeSys
Product Or Component Type:
contactor
Inrush Power In Va:
300-300 VA 60 Hz cos phi 0.8 (at 20°C)
Net Weight:
2.86 kg
Pollution Degree:
3
Heat Dissipation:
3-8 W at 60 Hz
Associated Fuse Rating:
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit
Flame Retardance:
V1 conforming to UL 94
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Weight:
2.86 kg
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 460 V DC
Maximum Operating Rate:
2400 cyc/h 60°C
$673.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 200A resistive load rating. Contactor is supplied with a 120 VAC 60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 5.91 inches wide and 5.20 inches deep. It weighs 6.31 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.