Schneider Electric

Schneider Electric LC1D115004U7 IEC contactor, TeSys Deca, nonreversing, 200A resistive, 4 pole, 4 NO, 240VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D115004U7
MPN:
LC1D115004U7
Condition:
New
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
Range:
TeSys
Power Dissipation Per Pole:
24 W AC-1
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
[Ie] Rated Operational Current:
200 A (at <60°C) at <= 440 V AC AC-1 for power circuit
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit
Protective Cover:
with
Eu Rohs Directive:
Compliant with Exemptions
Hold-In Power Consumption In Va:
2-18 VA 60 Hz cos phi 0.3 (at 20°C) || 2-18 VA 50 Hz cos phi 0.3 (at 20°C)
Environmental Disclosure:
ENVPEP060301EN
Control Circuit Voltage Limits:
0.3...0.5 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55°C operational AC 50/60 Hz || 1...1.15 Uc 55-70°C operational AC 50/60 Hz
Pole Contact Composition:
4 NO
Flame Retardance:
V1 conforming to UL 94
Product Or Component Type:
contactor
Mechanical Durability:
8 Mcycles
Operating Altitude:
0...9842.52 ft (0...3000 m)
Inrush Power In Va:
280-350 VA 60 Hz cos phi 0.8 (at 20°C) || 280-350 VA 50 Hz cos phi 0.8 (at 20°C)
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Overvoltage Category:
III
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Control Circuit Type:
AC 50/60 Hz
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 460 V DC
Safety Reliability Level:
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Protective Treatment:
THIEC 60068-2-30
Depth:
132 mm
Rohs Exemption Information:
Yes
Contactor Application:
resistive load
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Certifications:
UL || CSA || GOST || RINA || BV || GL || LROS (Lloyds register of shipping) || DNV || CCC || UKCA
Pvc Free:
Yes
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Weight:
2.86 kg
Maximum Operating Rate:
2400 cyc/h 60°C
Pollution Degree:
3
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Poles Description:
4P
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
[Uc] Control Circuit Voltage:
240 V AC 50/60 Hz
Mounting Support:
plate || rail
Mercury Free:
Yes
Net Weight:
2.86 kg
Associated Fuse Rating:
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Device Short Name:
LC1D
$673.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 200A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 5.91 inches wide and 5.20 inches deep. It weighs 6.31 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose