Schneider Electric

Schneider Electric LC1D1156G7 IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D1156G7
MPN:
LC1D1156G7
Condition:
New
[Ie] Rated Operational Current:
200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 115 A (at <60°C) AC AC-3e for power circuit
Circularity Profile:
ENVEOLI100405EN
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Mounting Support:
plate || rail
Auxiliary Contact Composition:
1 NO + 1 NC
Ip Degree Of Protection:
IP20 front face IEC 60529
Rohs Exemption Information:
Yes
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Device Short Name:
LC1D
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Product Certifications:
UL || CSA || CCC || UKCA || CE || EAC || Marine
Height:
158 mm
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Pole Contact Composition:
3 NO
Compatibility Code:
LC1D
Depth:
136 mm
Power Dissipation Per Pole:
24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Environmental Disclosure:
ENVPEP060301EN
Country of Origin:
Czechia
Inrush Power In Va:
280-350 VA 60 Hz cos phi 0.8 (at 20°C) || 280-350 VA 50 Hz cos phi 0.8 (at 20°C)
Contactor Application:
resistive load || motor control
Heat Dissipation:
3-8 W at 50/60 Hz
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Range:
TeSys
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Range Of Product:
TeSys Deca
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Fire Resistance:
850°C IEC 60695-2-1
Weight:
2.5 kg
Insulation Resistance:
> 10 MOhm for Signaling circuit
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mechanical Durability:
8 Mcycles
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Flame Retardance:
V1 conforming to UL 94
Minimum Switching Current:
5 mA for Signaling circuit
Pollution Degree:
3
Overvoltage Category:
III
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Sustainable Offer Status:
Green Premium product
Control Circuit Type:
AC 50/60 Hz
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Poles Description:
3P
Operating Time:
6...20 ms opening || 20...50 ms closing
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose